EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 48 of 116
DIGITAL OUTPUTS
In c-pro 3 EXP hecto+.
Digital outputs 1, 2, 3, 4 and 5 (electromechanical relays).
Terminal Meaning
CO1/2 common digital outputs 1 and 2
NO1 normally open contact digital output 1
NO2 normally open contact digital output 2
NO3 normally open contact digital output 3
CO3/4/5 common digital outputs 3, 4 and 5
CO3/4/5 common digital outputs 3, 4 and 5
NO4 normally open contact digital output 4
NO5 normally open contact digital output 5
Digital output 6 (electromechanical relay).
Terminal Meaning
CO6 common digital output 6
NO6 normally open contact digital output 6
NC6 normally closed contact digital output 6
The maximum length of the connecting cables of the digital outputs is 100 m (328 ft).
ANALOG OUTPUTS (in c-pro 3 EXP hecto only)
Analog outputs.
Terminal Meaning
VDC power supply driving analog output 1 (24 VDC, 50 mA max.)
AO1 analog output 1 (PWM signal)
GND ground
AO2 analog output 2 (configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V signal)
AO3 analog output 3 (configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V signal)