EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 47 of 116
The maximum length of the connecting cables of the CAN port depends on the baud rate of the CANbus communication, as
follows:
- 1,000 m (3,280 ft) with baud rate 20,000 baud
- 500 m (1,640 ft) with baud rate 50,000 baud
- 250 m (820 ft) with baud rate 125,000 baud
- 50 m (164 ft) with baud rate 500,000 baud.
Connect the CAN port using a twisted pair.
For the settings about the CAN port look at chapter 6 “CONFIGURATION”.
DIGITAL OUTPUTS
In c-pro 3 EXP hecto.
Digital outputs 1, 2, 3, 4 and 5 (electromechanical relays).
Terminal Meaning
CO1/2 common digital outputs 1 and 2
NO1 normally open contact digital output 1
NO2 normally open contact digital output 2
CO3 common digital output 3
NO3 normally open contact digital output 3
CO4/5 common digital outputs 4 and 5
NO4 normally open contact digital output 4
NO5 normally open contact digital output 5
Digital output 6 (electromechanical relay).
Terminal Meaning
CO6 common digital output 6
NO6 normally open contact digital output 6
NC6 normally closed contact digital output 6
The maximum length of the connecting cables of the digital outputs is 100 m (328 ft).
The maximum current allowed on the loads is 10 A.