EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 113 of 116
3 non optoisolated ports:
1 CAN port with
CANbus
communication
protocol
1 RS-485 port with
Modbus master /
slave
communication
protocol
(configurable via
application
software)
1 programming
and debugging
port.
4 non optoisolated ports (5
in c-pro 3 NODE mega):
1 CAN port with
CANbus communi-
cation protocol
1 CAN or MP-Bus
port (according to
the model, only in
c-pro 3 mega+)
1 RS-485 port with
Modbus slave
communication
protocol
1 RS-485 port with
Modbus master /
slave
communication
protocol
(configurable via
application
software)
1 programming
and debugging
port
1 port for gateway
c-pro 3 plug-in
(only in c-pro 3
NODE mega).
Power supply user interface:
24 VDC, 122 mA max.
The controller incorporates a
restorable thermal protection
of the power supply against
the short circuit and the
overload.
2 non optoisolated ports:
1 CAN port with
CANbus
communication
protocol
1 port to update
the firmware of the
expansion.
Microprocessor:
16 bit.
Program memory (FLASH):
c-pro 3 hecto and c-pro 3
hecto+
c-pro 3 mega, c-pro 3
mega+ and c-pro 3 NODE
mega
c-pro 3 EXP hecto and
c-pro 3 EXP hecto+
288 KB. 544 KB. -
Data memory (RAM):
c-pro 3 hecto and c-pro 3
hecto+
c-pro 3 mega, c-pro 3
mega+ and c-pro 3 NODE
mega
c-pro 3 EXP hecto and
c-pro 3 EXP hecto+
12 KB. 24 KB. -