C-PRO NANO AND MICRO NAV APPLICATION MANUAL
Page 20
tFLo Flow alarm delay during normal functioning 1 0 240 sec LEV2
tCoM Communication alarm delay 10 1 99 sec LEV2
SET1
Summer condensation high temperature alarm
set point (chiller)
100.0 80.0 115.0 °C LEV2 Note 1
diF1
Summer condensation high temperature alarm
differential (chiller)
5.0 1.0 15.0 °C LEV2 Note 1
SET2
Summer evaporation low temperature alarm
set point (chiller)
0.0 -15.0 5.0 °C LEV2 Note 1
diF2
Summer evaporation low temperature alarm
differential (chiller)
5.0 1.0 15.0 °C LEV2 Note 1
SET3
Winter evaporation low temperature alarm set
point (heat pump)
-9.0 -15.0 0.0 °C LEV2 Note 1
diF3
Winter evaporation low temperature alarm
differential (heat pump)
5.0 1.0 15.0 °C LEV2 Note 1
SET4
Winter condensation high temperature alarm
set point (heat pump)
115.0 90.0 120.0 °C LEV2 Note 1
diF4
Winter condensation high temperature alarm
differential (heat pump)
5.0 1.0 15.0 °C LEV2 Note 1
dAL1
Delta 1 : temperature difference AI1 – AI2
that signals alarm (summer chiller)
9.0 0.0 20.0 °C LEV2 Note 1
EAL1
Enable Delta 1 : temperature value below
which the probe AI1 must be found
20.0 0.0 50.0 °C LEV2 Note 1
dAL2
Delta 2 : temperature difference AI1 – AI2
that signals alarm (summer chiller)
-2.0 -10.0 0.0 °C LEV2 Note 1
dAL3
Delta 3 : temperature difference AI2 – AI1
that signals alarm (winter heat pump)
11.0 0.0 20.0 °C LEV2 Note 1
EAL3
Enable Delta 3 : temperature value above
which the probe AI1 must be found
35.0 0.0 50.0 °C LEV2 Note 1
dAL4
Delta 4 : temperature difference AI2 – SETH
that signals alarm (winter heat pump)
2.0 0.0 20.0 °C LEV2 Note 1
tAL4
Delta 4 alarm by-pass time
30 0 999 sec LEV2
nDeL
Number of interventions/hour of the Delta
alarms so that the alarm becomes manual
1 0 9 LEV2
tDeL
Activation delay time of the Delta alarms from
compressor switch-on
10 0 999 sec LEV2
dSF
Minimum difference |AI1 – AI2| from
compressor start-up that signals the ASF
Phases Sequence alarm
0.8 0.0 2.0 °C LEV2 Note 1
tSF
Phases Sequence alarm activation delay time
from compressor start-up
100 0 999 sec LEV2
ADMINISTRATOR PARAMETERS
nUM
Sets the number of slave units connected to the
master
2 0 4 LEV3
UdM
Sets the temperature unit of measurement:
0: °Celsius
1: °Fahrenheit
0 (°C) 0 1 LEV3
Addr
Board Modbus Address
1 1 247 LEV3
bAud
Baud Rate of the boar communication
(1=2400, 2=4800, 3=9600, 4=19200)
3 1 4 LEV3
Equal
ModBus Parity (0=none, 1=Odd, 2=Even)
2 0 2 LEV3
StoP
StopBit ModBus (0=1bit, 1=2bit)
0 0 1 LEV3
PDI1
Sets the digital input logic used for the flow
switch:
0: Normally open NO
NO NO (0) NC (1) LEV3
NC = flow
OK