Strona 1 - CROSS FLOW HEAT RECOVERY

PROGRAMMABLE CONTROLLER FOR AIR HANDLING UNITS WITH CROSS FLOW HEAT RECOVERY APPLICATION MANUAL CODE 144SAV

Strona 2

C-PRO MICRO SAVE APPLICATION MANUAL Page 10 Electric connections with 3-speed fans

Strona 3 - Summary

C-PRO MICRO SAVE APPLICATION MANUAL Page 11 2.2.2 I/O configuration with 1 speed fans + speed variator c-Pro MICRO CAN with 2 A/O V+V (code CPU1S0C2

Strona 4 - 1 GENERALITIES

C-PRO MICRO SAVE APPLICATION MANUAL Page 12 Electric connections with 1 speed fans + variator

Strona 5 - 2 Applications

C-PRO MICRO SAVE APPLICATION MANUAL Page 13 2.3 Connection lay out for C-PRO MICRO CAN Below find the connection lay out of the C-PRO MIC

Strona 6 - Page 6

C-PRO MICRO SAVE APPLICATION MANUAL Page 14 Connector 3: Connector for the analogue output (optional, not available in the day versions) Conn. Code

Strona 7 - PG03 parameter

C-PRO MICRO SAVE APPLICATION MANUAL Page 15 2.4 Connection lay out for C-PRO EXP MICRO CAN Below find the connection lay out of the expansion with

Strona 8 - 2.2 COMPLETE solution

C-PRO MICRO SAVE APPLICATION MANUAL Page 16 3 Network components and accessories

Strona 9 - probe (0-5 V) (Optional)

C-PRO MICRO SAVE APPLICATION MANUAL Page 17 4 User interface 4.1 Display and keyboard Both control solutions (compact and complete) use the Vg

Strona 10 - Page 10

C-PRO MICRO SAVE APPLICATION MANUAL Page 18 4.2 List of pages This paragraph presents the main pages and menus present in the application. The gener

Strona 11

C-PRO MICRO SAVE APPLICATION MANUAL Page 19 The range of values accepted for the passwords is: -999 / 9999. If no action is taken on a menu after 4

Strona 12 - Page 12

C-PRO MICRO SAVE APPLICATION MANUAL Page 2 Important Read these instructions carefully before installation and use and follow all recommendations re

Strona 13

C-PRO MICRO SAVE APPLICATION MANUAL Page 20 4.2.5 RTC Menu This menu contains the functionalities linked to the system RTC: ⋅ the setting of the cl

Strona 14

C-PRO MICRO SAVE APPLICATION MANUAL Page 21 4.2.7 Main OFF page The main OFF page changes depending on the reason why the unit is OFF.

Strona 15

C-PRO MICRO SAVE APPLICATION MANUAL Page 22 COMPLETE VERSION Alarm icon: appears when there are active alarms. If all of them have bee

Strona 16 - Page 16

C-PRO MICRO SAVE APPLICATION MANUAL Page 23 4.2.11 Log pages To display the alarms log, select HISTORIAN from the general menu or press ESC from th

Strona 17 - 4 User interface

C-PRO MICRO SAVE APPLICATION MANUAL Page 24 5 Configuration parameters Below are listed all parameters managed by the application. A br

Strona 18 - 4.2 List of pages

C-PRO MICRO SAVE APPLICATION MANUAL Page 25 Code Parameter description Default Min Max UM Menu Notes MAINTENANCE PM01 Max number

Strona 19 - 4.2.4 Installer Menu

C-PRO MICRO SAVE APPLICATION MANUAL Page 26 Code Parameter description Default Min Max UM Menu Notes Level 3 MANUFACTURER MENU C

Strona 20 - 4.2.6 Manufacturer Menu

C-PRO MICRO SAVE APPLICATION MANUAL Page 27 Code Parameter description Default Min Max UM Menu Notes ALARM PARAMETERS PA03 Enablin

Strona 21 - 4.2.8 Main ON page

C-PRO MICRO SAVE APPLICATION MANUAL Page 28 5.2 COMPLETE solution list of configuration parameters Code Parameter description Default Min Max U

Strona 22 - 4.2.10 Alarm pages

C-PRO MICRO SAVE APPLICATION MANUAL Page 29 Code Parameter description Default Min Max UM Menu Notes FANS PF01 Type of fans reg

Strona 23 - 4.2.11 Log pages

C-PRO MICRO SAVE APPLICATION MANUAL Page 3 Summary Important ...

Strona 24

C-PRO MICRO SAVE APPLICATION MANUAL Page 30 Code Parameter description Default Min Max UM Menu Notes VARIOUS PARAMETERS PH01 M

Strona 25

C-PRO MICRO SAVE APPLICATION MANUAL Page 31 Code Parameter description Default Min Max UM Menu Notes FANS PF06 Minimum time tha

Strona 26

C-PRO MICRO SAVE APPLICATION MANUAL Page 32 Code Parameter description Default Min Max UM Menu Notes ALARM PARAMETERS PA03 Enabli

Strona 27

C-PRO MICRO SAVE APPLICATION MANUAL Page 33 6 REGULATIONS 6.1 State of the unit There are several unit switch-on/off procedures: 1) Via the

Strona 28

C-PRO MICRO SAVE APPLICATION MANUAL Page 34 6.1.1 OFF state for alarm When the machine is active and an heavy alarm occurs the unit switches into th

Strona 29

C-PRO MICRO SAVE APPLICATION MANUAL Page 35 Set the PH99 parameter to “YES”(1) and wait until it becomes “NO”(0) again on the display. The system aut

Strona 30

C-PRO MICRO SAVE APPLICATION MANUAL Page 36 6.6 Functionality of the COMPACT control solution This control solution offers the base functionality

Strona 31

C-PRO MICRO SAVE APPLICATION MANUAL Page 37 6.6.1.5 Fans status Each of the two fans can be in the following working states: 1. OFF: the fan is OFF

Strona 32

C-PRO MICRO SAVE APPLICATION MANUAL Page 38 If the temperature T is between Tg and Tg + Tdiff (default 3°C, can be modified by parameter PF08) the cu

Strona 33 - 6 REGULATIONS

C-PRO MICRO SAVE APPLICATION MANUAL Page 39 6.6.3.1 Cyclical defrosting with minimum temperatures The set point must be determined along with

Strona 34 - 6.2 RTC setting

C-PRO MICRO SAVE APPLICATION MANUAL Page 4 1 GENERALITIES 1.1 Description The application is dedicated to the control and regulation of the A

Strona 35 - 6.5 Programming key

C-PRO MICRO SAVE APPLICATION MANUAL Page 40 6.7 Features of the COMPLETE control solution Al functions of the COMPACT version are included in this

Strona 36 - Page 36

C-PRO MICRO SAVE APPLICATION MANUAL Page 41 6.7.3 Fresh air intake damper It is possible to manage an optional motorised damper (can be enabled by p

Strona 37

C-PRO MICRO SAVE APPLICATION MANUAL Page 42 Anti-freeze safety on hot water circuit (AL04) The anti-freeze mechanical thermostat (digital input DI7)

Strona 38

C-PRO MICRO SAVE APPLICATION MANUAL Page 43 6.7.4.4 Heaters over temperature protection with automatic reset By setting the parameter PA16=1(hi

Strona 39

C-PRO MICRO SAVE APPLICATION MANUAL Page 44 7 DIAGNOSTICS The application can manage a series of alarms relevant to the fans and the

Strona 40 - 6.7.1 Post-Ventilation

C-PRO MICRO SAVE APPLICATION MANUAL Page 45 7.2 Alarms table Below is a list of all alarms managed by the application. The order of presentation is

Strona 41 - 6.7.4 Heating

C-PRO MICRO SAVE APPLICATION MANUAL Page 46 7.4 Alarms log The controller record the ALARMS LOG in a non-volatile area of the memory organised as F

Strona 42

C-PRO MICRO SAVE APPLICATION MANUAL Page 47 8 MODBUS VARIABLES The controller can be managed by a supervisor via Modbus protocol. The communi

Strona 43

C-PRO MICRO SAVE APPLICATION MANUAL Page 48 Bit4=AL20, Bit5=AL21, Bit6=AL22, Bit7=AL23, Bit8=Free, Bit9=AL25, Bit10=AL26, Bit11=AL27, Bit12=AL28, Bit

Strona 44 - 7 DIAGNOSTICS

C-PRO MICRO SAVE APPLICATION MANUAL Page 49 0x060D 1550 PT11a17_TypeDay[1] 0 0 1 0=Sunday,.. 6=Saturday R/W 0x060E 1551 PT11a17_TypeDay[2] 0

Strona 45 - 7.3 General alarm relay

C-PRO MICRO SAVE APPLICATION MANUAL Page 5 2 Applications 2.1 COMPACT solution The picture above shows a principle layout. It is intended for

Strona 46 - 7.4 Alarms log

C-PRO MICRO SAVE APPLICATION MANUAL Page 50 0x062A 1579 PF11_MinTimePostFan 30 0 999 sec R/W 0x062B 1580 PF12_SpeedFan_Confort_DI 3 1 3

Strona 47 - 8 MODBUS VARIABLES

C-PRO MICRO SAVE APPLICATION MANUAL Page 51 0x064C 1613 PA13_ThermalResistorAlarm_Rele 1 0 1 R/W 0x064D 1614 PA15_LimitSitwchAlarm_Rele 1

Strona 48

C-PRO MICRO SAVE APPLICATION MANUAL Page 52 0x066E 1647 PH55_Logic_DI5 0 0 1 0=NO, 1=NC R/W 0x066F 1648 PH56_Logic_DI6 1 0 1 0=NO, 1=NC

Strona 49

C-PRO MICRO SAVE APPLICATION MANUAL Page 53 Application manual C-PRO MICRO SAVE Version 1.01 of November 2010 Code 144SAVEU0E01. This publication is

Strona 50

OFFICES Evco Via Mezzaterra 6, 32036 Sedico Belluno ITALIA Tel. 0437-852468 Fax 0437-83648 [email protected] www.evco.it OVERSEES BRANCHES Control Fran

Strona 51

C-PRO MICRO SAVE APPLICATION MANUAL Page 6 Electric connections with 3-speed fans Note: For driving the 3-speed fans (Digital output) set PG10=DO

Strona 52

C-PRO MICRO SAVE APPLICATION MANUAL Page 7 Electric connections with 1 speed fans + variator Note: For driving the modulating fans (Analogue output

Strona 53 - Page 53

C-PRO MICRO SAVE APPLICATION MANUAL Page 8 2.2 COMPLETE solution The picture above shows a principle layout, it is intended for indicating the p

Strona 54

C-PRO MICRO SAVE APPLICATION MANUAL Page 9 2.2.1 I/O configuration with 3-speed fans c-Pro MICRO CAN with 2 A/O V+V (code CPU1S0C2V) c-Pro EXP MICRO