C-PRO MICRO SAVE APPLICATION MANUAL
Page 29
Code Parameter description Default Min Max UM Menu Notes
FANS
PF01
Type of fans regulation:
0: Manual
1: Automatic
2: Automatic with presence sensor
3: Automatic with CO
2
sensor
0 0 3 - IS-F
PF03 Fans speed in COMFORT period V2 V1 V3 - IS-F
PF04 Fans speed in ECONOMY period V1 V0 V2 - IS-F
PF05 Fans speed in RTC error V0 V0 V3 - IS-F
Only if
PF01=1/2 /3
PF12
Fans speed in COMFORT with presence
sensor active
V3 V1 V3 - IS-F
PF13 Speed in case of « non working » day V0 V0 V3 - IS-F
PF14 Set point CO
2
for Speed 1 and 2 500 PH03 PF15 ppm IS-F
Speed 1:
CO
2
< PF14
Speed 2:
CO
2
PF14
CO
2
< PF15
Speed 3:
CO
2
> PF15
PF15 Set point CO
2
for Speed 2 and 3 1100 PF14 PH04 ppm IS-F
PF21 Speed variator value corresponding to speed V1 33.50 0.00 100.00 % IS-F
PF22 Speed variator value corresponding to speed V2 66.50 0.00 100.00 % IS-F
PF23 Speed variator value corresponding to speed V3 100.00 0.00 100.00 % IS-F
Only version
with variator
HEATING COILS
This menu is only accessible if PG02>0
Pb01
Regulation probe for heating
0: Supply Probe
1: Return Probe
0 0 1 IS-B
FREECOOLING
Pr04
Outside air/recovery heat exchanger by-
pass temperature set point in summer
15.0 PH01 PH02
°C
°F
IS-FC
Pr05
Return air/recovery heat exchanger by-
pass temperature set point in summer
22.0 PH01 PH02
°C
°F
IS-FC
ALARM PARAMETERS
PA01 Enabling fans working hours alarm
Active
(1)
Not-
active (0)
Active (1) - IS-S
PA02
Signals working hours alarms on alarm
relay
No (0) No (0) Yes (1) - IS-S
PA04
Signals the supply/return fans thermal
overload alarm on the alarm relay
Yes (1) No (0) Yes (1) - IS-S
PA07
Differential pressure switch alarm delay on
unit start-up
60 0 999 sec IS-S
PA11
Signals the coil anti-freeze alarm on the
alarm relay
Yes (1) No (0) Yes (1) - IS-S
PA15
Signalling of the outside air damper limit
switch alarm on alarm relay
Yes (1) No (0) Yes (1) IS-S
Only if
PG02=1
PA21
Signalling of high/low temperature alarms
on the alarm relay
yes (1) No (0) Yes (1) IS-S
PA23
Signalling of expansion alarm on alarm
relay
Yes (1) No (0) Yes (1) IS-S
PA25 Signals RTC alarm on alarm relay Yes (1) No (0) Yes (1) - IS-S
PA27 Signals probe alarms on alarm relay Yes (1) No (0) Yes (1) - IS-S
Przeglądanie stron 28