EVCO S.p.A. c-pro 3 NODE kilo | Hardware manual ver. 1.0 | Code 114CP3NKE104
page 13 of 44
DIGITAL OUTPUTS
Digital outputs.
PART MEANING
CO1 common digital output 1
NO1
usually open contact for digital output 1
according to model:
-
electromechanical relay with 3 A res. @ 250 VAC
-
control for 24 VAC/DC, 600 mA max. solid state relays
CO2 common digital output 1
NO2
usually open contact for digital output 2
according to model:
-
electromechanical relay with 3 A res. @ 250 VAC
-
control for 24 VAC/DC, 600 mA max. solid state relays
CO3-6 common digital output 3... 6
NO3 usually open contact for digital output 3 (electromechanical relay with 3 A res. @ 250 VAC)
NO4 usually open contact for digital output 4 (electromechanical relay with 3 A res. @ 250 VAC)
NO5 usually open contact for digital output 5 (electromechanical relay with 3 A res. @ 250 VAC)
NO6 usually open contact for digital output 6 (electromechanical relay with 3 A res. @ 250 VAC)
CO7 common digital output 7
NO7 usually open contact for digital output 7 (electromechanical relay with 3 A res. @ 250 VAC)
NC7 usually open contact for digital output 7
CAN/RS-485
RS-485 MODBUS slave, RS-485 MODBUS master/slave and CAN CANBUS ports
The communication protocol for the RS-485 MODBUS master/slave port can be set with the UNI-PRO 3 development environment.
For the settings for the RS-485 MODBUS slave, RS-485 MODBUS master/slave and CAN CANBUS ports, please refer to chapter 6
“CONFIGURATION”.
PART MEANING
CAN+ CAN CANBUS port positive pole
CAN- CAN CANBUS port negative pole
GND RS-485 MODBUS slave, RS-485 MODBUS master/slave and CAN CANBUS ports ground
A1/+ RS-485 MODBUS master/slave port positive pole