page 15 of 55
TECHNICAL
DATA
".
POWER
Device power supply (24 VAC/DC not insulated)
If the device runs on direct current, it shall be necessary to pay attention to the polarity of the supply voltage.
If the device is connected to a network of devices, it shall be necessary to:
-
check that the power supply of the devices included in the network are galvanically isolated.
-
the phase powering the device is the same as that of all the devices included in the network.
PART MEANING
AC/+
device power supply:
-
if the device is run by alternating current, connect the phase
-
if the device is run by direct current, connect the positive pole
AC/-
device power supply:
-
if the device is run by alternating current, connect the neuter
-
if the device is run by direct current, connect the negative pole