WORKING SETPOINT
Label Min. Max. U.m. Stand. Working setpoint
rA1 rA2 °C 0 first working setpoint
rb1 rb2 °C 0 second working setpoint
CONFIGURATION PARAMETERS
Label Min. Max. U.m. Stand. Password
PA -90 100 --- 0 password (§)
Label Min. Max. U.m. Stand. Kind of regulator
-/0 1 3 --- 2 kind of regulator
Label Min. Max. U.m. Stand. Measure input
/0 01 31 --- (*) kind of probe
/1 -9 +10 °C 0 calibration
/2 0 6 --- 3 digital filter
/4 0 1 --- 0 leading zeroes displaying
/5 0 1 --- 1 decimal point
/6 -99 +999 points -20 lower end of scale for 0/4-20 mA input (it coincides with the mini-
mum calibration value of the transducer)
/7 -99 +999 points +80 upper end of scale for 0/4-20 mA input (it coincides with the maxi-
mum calibration value of the transducer)
Label Min. Max. U.m. Stand. ON-OFF temperature regulator associated to the first/
second working setpoint and to the output K 1/K 2
rA0/rb0 -99 +99 °C (*) hysteresis (differential) (§)
rA1/rb1 -99 +999 °C (*) minimum working setpoint programmable
rA2/rb2 -99 +999 °C (*) maximum working setpoint programmable
rA3/rb3 0 1 --- 1 “cooling” or “heating” functioning
rA4/rb4 0 1 --- 0 kind of hysteresis (kind of differential)
rA5/rb5 0 1 --- 0 locking of the working setpoint modification
Label Min. Max. U.m. Stand. Output K 1/K 2 protection
CA0/Cb0 0 999 sec. 0 disabling time to the output activation from the instrument start
CA1/Cb1 0 999 sec. 0 disabling time to the output activation from the previous activation
CA2/Cb2 0 999 sec. 0 disabling time to the output activation from the previous deactiva-
tion
CA3/Cb3 0 1 --- 0 output status during a probe failure alarm
CA4/Cb4 0 1 --- 0 disabling time to the output activation and deactivation
Label Min. Max. U.m. Stand. Temperature alarm regulator associated to the first/sec-
ond temperature alarm
AA0/Ab0 (*) +99 °C (*) hysteresis (differential)
AA1/Ab1 -99 +999 °C 0 alarm setpoint
AA3/Ab3 0 999 min. 0 disabling time to the alarm activation from the instrument start
AA4/Ab4 1 7 --- 1 kind of alarm
2 3
and or do not operate with the keys
for fifty seconds at least.